dakkoepel plat dak dakkoepel plat dak

OUR SHE SYSTEMS



Discover our advanced smoke and heat extraction (SHE) systems, designed to keep your working environment safe. In the event of fire or smoke, our reliable SHE solutions ensure safe extraction and minimise damage. Safety first thanks to Skylux.

SKYLUX 160° CE

Skylux 160° CE: an electric modular system for effective smoke and heat extraction for industrial or utility buildings

DISCOVER OUR RANGE AND POSSIBILITIES

SKYLUX SKYMAX CE

Skymax CE: a specially designe smoke and heat extraction system for ventilation in interior stairwells

DISCOVER OUR RANGE AND POSSIBILITIES

Even more features

This system improves roof accessibility and performance and offers a fast installation and excellent insulation (Rw up to 40 dB, U-value up to 0.51 W/m²K). It provides efficient ventilation, flexible central unit placement and is designed for optimal air flow. The versatility is enhanced by various curb combinations and finishes, including a plastic or glass skylight.

Product Type CE certification NBN Utp (W/m²K) Urc (W/m²K)
Skylux 160° CE SHE EN 12101-2:2003 S21-208-1 1.19 1.12 (for daylight size 110x110 cm and PVC curb 30/20)
Skylux Skymax CE SHE EN 12101-2:2003 S21-208-3:2018 1.28 1.32
Dimensions 100x130 – 100x110 – 120x120 are in accordance with NBN S-21-208-3:2018 for buildings > 10 metres.
Wat is het verschil tussen de Skycom CE-Master en de Skycom CE-Slave centrales?
Hoeveel Skycom CE-Slave centrales zijn er nodig voor mijn brandzone?
Kan een Skycom CE-Slave centrale meerdere motoren aansturen?
Wat zijn de mogelijkheden voor het aansluiten van motoren op een Skycom CE-Slave centrale?
Wat gebeurt er als een openingssysteem mechanische positieve veiligheid heeft?
Skycom Skymax CE control unit Skycom CE Master control unit Skycom CE Slave control unit
Type (specific) Control unit for Skymax CE One zone basic control for electric SHE systems Supplement to Skycom CE Master
Specifications Stairwell, does not open automatically Alarm and fresh air ventilation, LED indication on front panel Extension control unit, integrated temperature sensor
Colour White RAL 9003 White RAL 9003 White (inside and outside)
Max. output current 5 A 8 A 8 A
Supply voltage 230 V AC - max. 150 VA 230 V AC - max 1.1 A 320 V
Output voltage 24 V DC 24 V DC 24 V
Dimensions(b x h x d) - 286 x 238 x 113 mm 286 x 238 x 113 mm
Standards According to NBN S21-208-3:2018, EN 12101-10, prEN 12101-9 According to EN 12101-10, prEN 12101-9 -
Bijzonderheden 72 hours assured operation, priority switch is necessary - 24 V
Wiring diagram Download Download Download
Externe prioritaire schakelaar voor brandweer
Aid for fire brigade

Priority switch

If the Skycom CE control unit cannot be installed near the entrance door, it is necessary to install a priority switch. Thanks to the presence of a priority switch in the entrance hall, firemen can easily operate the SHE system.

  • Specifically designed for use with Skycom CE.
  • Holds the highest priority status within the system.
  • Provided with LED lights to indicate opening and closing.

The control unit can be installed in a technical room for example. The priority switch, not supplied as standard with the Skycom CE Master control unit, has the highest priority in the system and measures 125 mm x 125 mm x 36 mm.

TECHNICAL FILE & WIRING DIAGRAM